The brightness sensor HFA/A registers the brightness from 0-100 kLux using a photo-diode and, optionally, also the temperature from 0...+50°C. For further processing the transducer converts the measuring result into a linear output signal 0-10 V respectively 4-20 mA. 8 different measuring ranges be selected (0-0.5 kLux, 0-1 kLux, 0-2 kLux, 0-5 kLux, 0-10 kLux, 0-20 kLux, 0-50 kLux, 0-100 kLux) which can be switched, according to requirements, by the innovative DIP switching technology. The robust housing is defined especially for outdoor use. The brightness sensor is optimally suited for an energy efficient control of buildings, such as e.g. controlling the lighting in offices, industrial facilities etc..
- Measurement range brightness 0-0,5 kLux, 0-1 kLux, 0-2 kLux, 0-5 kLux, 0-10 kLux, 0-20 kLux, 0-50 kLux, 0-100 kLux
- Measurement range temp. 0...+50°C
- Accuracy ±10% FS (20°C)
- Temperature dependency ±5% FS / 10 K
- Response time (t90) < 1 s
- Linearity inaccuracy < ±5% final value
- Offset ±10% from the selected measuring range by 270° potentiometer
- Sensor Brightness: photodiode, Temperature: resistance sensor
- Sensor protection mounted inside housing
- Running-in time < 3 s
- Supply voltage analog 0-10 V 24 V AC/DC (±5%)
- Supply voltage analog 4-20 mA 15...36 V DC (Ubmin = 15 V + RLoad*0,02A)
- Current consumption at 0-10 V typ. 10 mA
- Current consumption at 4-20 mA max. 20 mA / output
- Analogue output 0-10 V 3-wire connection, min. load resistance 100 kOhm
- Analogue output 4-20 mA 2-wire connection (transmitter), max. RLoad(Ohm) = (+Ub - 15 V) / 0,02 A
- Switching Hysteresis Relay 2% of the selected scaling (without display), 0,5...5% of the selected scaling adjustable (with display)
- Electrical connection screw terminals max. 1,5 mm²
- Housing Polycarbonate PC UL 94 V0 with hinge locks, color signal white similar to RAL 9003
- Cable gland PG11 high-strength cable gland with strain relief
- Dimensions Housing: L 89 x W 80 x H 47 mm, Protection sleeve: Ø 6 x 45 mm
- Protection type IP65
- Protection class III
- Working range r.H. 0...98% r.H. in contaminant-free, non-condensing air
- Working temperature Electronic: -20...+50°C
- Storage temperature -20...+50°C
- Installation screw fastening
- Approvals CE, EAC, RoHS